ZJH Series Pneumatic Diaphragm Control Ball Valve
Benefits Of Pneumatic Control Valve:
COVNA Pneumatic Control Valves are suitable for regulating flow rate of pipelines. Pneumatic control valve is powered by compressed air, without electricity, safe and explosion-proof. The positioner receives and feedback the control signal of the industrial automation control system to complete the adjustment of the flow and pressure of the pipeline medium. Widely used in shipbuilding, power plants, food and beverage, and so on.
Features Of ZJH Series Pneumatic Diaphragm Control Valve:
● Globe valve is driven by pneumatic control which could allow your automation more easily and help you control the medium more precise
● Available in single-seat type and sleeve type for your choice
● Precise control: Pneumatic control valves offer precise and accurate control over the flow of fluids and gases
Technical Parameters Of Pneumatic Control Valve:
Nominal Size DN (mm) | 20 | 25 | 32 | 40 | 50 | 65 | 80 | 100 | 125 | 150 | 200 | 250 | 300 | ||||
10 | 12 | 15 | 20 | ||||||||||||||
Rated Flow Coefficient CV | High accuracy flow characteristic clack | 1.6 | 2.5 | 4.0 | 6.3 | 10 | 17 | 24 | 44 | 68 | 99 | 175 | 275 | 360 | 630 | 900 | 1440 |
High capacity flow characteristic clack | 1.8 | 2.8 | 4.4 | 6.9 | 11 | 21 | 30 | 50 | 85 | 125 | 200 | 310 | 440 | 690 | 1000 | 1600 | |
Rated Stroke(mm) | 10 | 16 | 25 | 40 | 60 | 100 | |||||||||||
Effective Diaphragm Area cm2 | 280 | 400 | 630 | 1000 | 1600 | ||||||||||||
Inherent Regulation Ratio | 50:1 | ||||||||||||||||
Nominal Pressure MPa | 1.6 / 4.0 / 6.4 | ||||||||||||||||
Service Temperature | -100~-60℃; -200~-100℃; -250~-200℃ | ||||||||||||||||
Ambient Temperature | -30~70℃ | ||||||||||||||||
Air Supply Pressure KPa | 0.14 / 0.25 / 0.40 | ||||||||||||||||
Spring Range KPa | 20~100(Basic type) / 40~200 / 80~240 | ||||||||||||||||
Connection Thread | G1/4" , M16X1.5 |
Major Technological Performance Indexes And Testing:
1. Major performance indexes shall be as shown in below table
2. Testing shall be conducted according to the specification of GB/T4213-92
Serial No. | Technical Performance | Without Positioner | With Positioner |
1 | Basic Error | ≤±5% | ≤±1% |
2 | Return Difference | ≤3% | ≤1% |
3 | Dead Zone | ≤3% | ≤0.4% |
4 | Leakage | ZJHP Type:≤1X10-4Rated FlowZJHM Type:≤1X10-3 Rated Flow | |
5 | Rated Flow Coefficient | ≤±10% | |
6 | Inherent Flow Characteristic | Slope±30% |
Dimension: